The AHG2015 fire display panels are specifically designed for the AHGBUS circular loop technology, and occupy an address point of the bus. In the event of a fire, the fire location is displayed through switching on the related LED indicator lamp on the fire disp lay panel. The indicator lamps are programmable. Functional Features: Built-in microcontroller; Low power design and the standby current is not over 80μA; Built-in bar code and automatic identifying and addressing software; Saving installation time and manual work due to none manual setting such as electronic addressing; Making an automatic test on its operation through its perfect self-diagnostic function; The panel can program each LED indicator lamp on the module; Sending a continuous sound and light alarm in event of a fire; The sound alarm can be silenced timely through the equipped mute button; The panel can conduct a state and analog alarm test on any indicator lamp set on the fire display panel. Technical data Moudle : HX-DZ/32-AHG2015 Operating Voltage : DC19V Operating Current : ≤80μA External Connection Voltage : DC24V External Connection Electric Current : ≤200mA Ambient Temperature : -10℃~55℃ Relative Humidity : ≤95% RH Weight : 1600g Dimensions (W X H X D) : 232mm?—162mm?—63mm |